GC SPEC #06/A137 GC ITEM NUMBER CABLE: 3 CORE 6MMSQ+2.5MMSQ EARTH PAC CONDUCTOR XLPE INSULATED LAID UP, PVC BEDDING, SWA, PVC SHEATH STANDARD: GENERALLY TO IEC60502-1 1998 600/1000 VOLTS CONDUCTOR:PLAIN ANNEALED COPPER STRANDING:7/1.04MM SHAPE:CIRCULAR COMPRESSED CSA 6MM² DIA/DEPTH (MM): 3.06 MIN 3.06 NOM 3.06 MAX INSULATION:AC SPARK TEST TO 6KV EXTRUDED : XLPE COMPOUND TYPE OR EQUIVALENT COLOURS: RED, WHITE (NAT), BLUE RADIAL: MIN AV 0.70MM MAX AV 0.77MM MIN PT 0.53MM DIA/DEPTH (MM): 4.46 MIN 4.53 NOM 4.60 MAX EARTH CONDUCTOR: PLAIN ANNEALED COPPER STRANDING: 7/0.67 SHAPE : CIRCULAR COMPRESSED C.S.A : 2.5MMSQ
INSULATION:AC SPARK TEST TO 6KV EXTRUDED : XLPE COMPOUND TYPE OR EQUIVALENT COLOURS: GREEN/YELLOW RADIAL: MIN AV 0.60 MAX AV 0.66 MIN PT 0.44 DIA/DEPTH (MM) : 3.17 MIN 3.23 NOM 3.29 MAX
LAY UP: CORES LAID UP TO A CIRCULAR CONSTRUCTION 3 CORE + E STAGE DIA/DEPTH (MM) : 10.16 MIN 10.33 NOM 10.49 MAX
BEDDING: EXTRUDED VD26 COMPOUND TYPE OR EQUIVALENT COLOUR: BLACK RADIAL (MM): MIN AV 1.00 MAX AV 1.10 MIN PT 0.60 DIA/DEPTH (MM): 12.16 MIN 12.43 NOM 12.69 MAX
ARMOUR:GALVANISD STEEL WIRE L/H LAY DIRECTION # OF WIRES 31 RADIAL (MM) : 1.25 DIA/DEPTH (MM): 14.66 MIN 14.93 NOM 15.19 MAX
|
SHEATH: EXTRUDED VD26 COMPOUND TYPE OR EQUIVALENT COLOUR: GREY(OR AS REQUESTED) WITH UV STABILISER RADIAL (MM): MIN AV 1.80 MAX AV 1.98 MIN PT 1.24 DIA/DEPTH (MM): 18.26 MIN 18.71 NOM 19.15 MAX
IDENTIFICATION: SHEATH EMBOSSED/PRINTED: (MANUFACTURERS NAME) X-90 ELECTRIC CABLE 600/1000 VOLT 6MMSQ CU 3C+EARTH (YEAR OF MANUFACTURE) INTERVAL EVERY 500MM PLUS SEQUENTIAL MARKING WITH ZERO AT DRUM END OF CABLE
TESTING: TEST TO IEC60502 INSULATION RESISTANCE TO BE RECORDED TEST CERTIFICATE REQURIED NOTE:MANUFACTURING TOLERANCES MAY ALLOW PRODUCT DIMENSIONS TO LIE OUTSIDE ABOVE QUOTED VALUES
MODIFICATIONS: 06/11/06 ORIGINAL LB(GC)
|