GC SPEC #06/A126 GC ITEM NUMBER CABLE: 4 CORE 70MMSQ+EARTH XLPE LS SWA PVC 600/1000 VOLT STANDARD: GENERALLY TO IEC60502-1 1998 600/1000 VOLTS CONDUCTOR:PLAIN ANNEALED COPPER STRANDING:19/2.24MM SHAPE:90 DEG SECTOR CSA 70MM² DIA 8.96MM
INSULATION:EXTRUDED XLPE COLOUR: RED, WHITE, BLUE, BLACK RADIAL: MIN AV 1.10MM MAX AV 1.21MM DIA: MIN 11.11MM MAX 11.43MM
LAY UP:4 CORE CIRCULAR, R/H LAY BINDER: 1X0.025 POLYESTER OR POLYPROPYLENE TAPE WITH 10% OVERLAP BEDDING:EXTRUDED PVC COMPOUND COLOUR:BLACK DIA.:MIN 27.94MM MAX 28.91MM
COPPER EARTH SCREEN: PLAIN ANNEALED COPPER WIRE SIZE:1.13MM # OF WIRES 25 WIRES SPACED EQUALLY AROUND CABLE
LEAD SHEATH:EXTRUDED LEAD ALLOY E 2 x RIPCORDS LAID UNDER SHEATH RADIAL:MIN 1.60MM MAX 1.76MM DIA:MIN 30.20MM MAX 31.17MM
BEDDING: EXTRUDED PVC COMPOUND COLOUR: BLACK RADIAL: MIN AV 1.30MM MAX AV 1.43MM DIA: MIN 36.00MM MAX 37.55MM
ARMOUR:GALVANISD STEEL WIRE L/H LAY DIA: 2.50MM # OF WIRES 45 DIA: MIN 41.00MM MAX 42.55MM
SHEATH: EXTRUDED PVC COMPOUND COLOUR: GREY RADIAL: MIN AV 2.60MM MAX AV 2.86MM DIA: MIN 46.20MM MAX 48.27MM IDENTIFICATION: SHEATH EMBOSSED/PRINTED: (MANUFACTURERS NAME) XLPE ELECTRIC CABLE 600/1000 VOLT 4 CORE 70MMSQ+EARTH (YEAR OF MANUFACTURE)
DRUM LENGTH:TO BE 500 OR 1000 METRE ONLY UNLESS SPECIFIED OTHERWISE UNDER RUN OF LESS THAN 2.5% OR OVER RUN OF LESS THAN 5% ONLY ALLOWABLE
|
CABLE DRUMS:TO BE CONSTRUCTED OF TANALISED TIMBER
THREE COPIES OF TEST CERTIFICATES MUST BE SUPPLIED WITH CABLE
ALL DOCUMENTS RELATING TO THIS ORDER MUST SHOW NZRC ORDER NUMBER IN FULL
CABLE XLPE LS SWA 4X70MM2+EARTH
NOTE: MANUFACTURING TOLERANCES MAY ALLOW PRODUCT DIMENSIONS TO LIE OUTSIDE ABOVE QUOTED VALUES
MODIFICATIONS: 06/11/06 ORIGINAL LB(GC)
CABLE GLAND = BICON 50A RTLF
|